SEARCH PRODUCTS
PRODUCTS

Specification
- Extremely flat and integrated housing design with spring clamps for easy and quick installation.
- With two channels for lighting & HVAC control.
- To enlarge the detection range by connecting the slave detector to master detector, max. 10pcs slave detectors can be connected.
- Can be programmed by IR remote control for easy and quick settings, especially to provide alternative function of auto / semi-auto mode (note: The IR remote control is strongly recommended to purchase).
- The ambient Lux value can be learned as the threshold for switching on / off the loads.
- A red LED is equipped as an indicator for test triggering and IR setting.
- Rated Voltage : 220 - 240V~ 50 / 60Hz
- Load :
- LoadⅠ(CH1) for Lighting
- Incandescent Lamp: max. 2000W
- AC Halogen Lamp: max. 1000W
- LV Halogen Lamp: max. 1000VA / 600W
- Fluorescent Lamp: max. 900VA / 100μF
- 25 x (1 x 18W); 15 x (1 x 36W); 10 x (1 x 58W)
- 12 x (2 x 18W); 7 x (2 x 36W); 5 x (2 x 58W)
- max. 1000VA / 600W (uncompensated)
- LED Lamp: max. 400W
- Energy Saving Lamp: max. 600VA / 400W (include CFL & PL lamp)
- Load Ⅱ(CH2) for HVAC (voltage free contact):
- Max. 5A (cosφ=1) for ≦250VAC
- Max. 5A for ≦30VDC
- Max. 1A (cosφ=0.4) for ≦250VAC
- Detection Range: 360º circular, up to Φ9m at height of 2.5m
- Lux Adjustment: adjustable from approx. 5Lux to 2000Lux and Learning (range: 5Lux - 2000Lux)
- Auto Off Time Adjustment:
- Time 1 (for lighting): adjustable from approx. 5sec to 30min and Test & Short impulse (1sec)
- Time 2 (for HVAC) : adjustable from approx. 10sec to 60min
- Environmental Protection: IP44
- Operating Temperature: -20°C to +45°C
Highlight

Dimension

Detection